SS 563-2:2010 (2017)
[Confirmed]
Code of practice for the design, installation and maintenance of emergency lighting and power supply systems in buildings - Part 2 : Installation requirements and maintenance procedures
...SS 563-2:2010(2017)+A2:2017
14
COPYRIGHT
For case (b), the luminaires shall be arranged throughout the designated area in such a manner as to
ensure that the visual conditions, are not inferior to those provided by the emergency lighting install...
...NOTE The purpose of the measures prescribed above is to prevent a period of total darkness following a short
interruption to the supply, because with certain types of discharge lamps a delay of 3 min to 6 min may occur before
the lamps can restrike...
...Loss of supply shall be sensed at the
load side of the device protecting the final circuit...